3.2 Nominal data
Motor M8E110-EF
Phase 1~ 1~
Nominal voltage / VAC 230 230
Frequency / Hz 50 60
Type of data definition ml ml
Valid for approval /
standard
CE CE
Speed / min
-1
665 740
Power input / W 130 170
Current draw / A 0.59 0.75
Motor capacitor / µF 3 3
Capacitor voltage / VDB 400 400
Capacitor standard P0 (CE) P0 (CE)
Max. back pressure / Pa 35 45
Min. ambient temperature
/ °C
-40 -40
Max. ambient
temperature
/ °C
65 65
Starting current / A 1.2
Maximum safe operating
speed / min
-1
1920
@ 55 °C
1920
@ 55 °C
ml = Max. load · me = Max. efficiency · fa = Running at free air
cs = Customer specs · cu = Customer unit
Subject to alterations
3.3 Technical features
Mass 11.8 kg
Size 500 mm
Surface of rotor Coated in black
Material of terminal box PC/ABS plastic, black
Material of blades Press-fitted sheet steel blank, sprayed
with PP plastic
Material of guard grille Steel, phosphated and coated in black
plastic
Number of blades 5
Direction of air flow "V"
Direction of rotation Counter-clockwise, seen on rotor
Type of protection IP 54
Insulation class "F"
Humidity class F4-1
Mounting position Shaft horizontal or rotor on bottom; rotor
on top on request
Condensate discharge
holes
Rotor-side
Operation mode S1
Motor bearing Ball bearing
Touch current acc.
IEC 60990 (measuring
network Fig. 4, TN
system)
<= 3.5 mA
Electrical leads Via terminal box, integrated capacitor
connected via terminal box
Motor protection Thermal overload protector (TOP)
brought out
Cable exit Axial
Protection class I (if protective earth is connected by
customer)
Product conforming
to standard
EN 61800-5-1; CE
Approval EAC; UL 1004-1; VDE; CCC; CSA
C22.2 Nr.100
For cyclic speed loads, note that the rotating parts of the device
are designed for maximum one million load cycles. If you have
specific questions, contact ebm-papst for support.
3.4 Mounting data
; Secure the mounting screws against accidentally coming loose (e.g.
by using self-locking screws).
Strength class for
mounting screws
8.8
You can obtain additional mounting data from the product drawing if
necessary.
3.5 Transport and storage conditions
; Use the device in accordance with its protection type.
Max. permissible
ambient motor temp.
(transp./ storage)
+ 80 °C
Min. permissible
ambient motor temp.
(transp./storage)
- 40 °C
Item no. 10098-5-9970 · Revision 82542 · Release 2014-05-08 · Page 5 / 11